5.1.9 |
Setting Flow Rates
DO NOT apply high pressure directly to Leeaky Hose, as this will damage it. If
you see a lot of little spurters, the pressure is too high. Leeaky Hose is a slow
soaker system and is not designed for high flow rates.
Leeaky Hose may be used if you have a high pressure water supply, however
you will need to regulate the flow of water running into the Leeaky Hose by
means of pressure reducing valve before an in-line tap set to no more than
75kPa (10.5psi).
If using an in-line tap you need to do the following calculations in order to set
the flow rate:
The nominal rate of leakage is 2 litres per metre per hour. If, for example, you
are running a 30 metre length of Leeaky Hose, the amount of water required
to be delivered to the soil in an hour over the length of the hose would be 60
litres. Divide the total volume (in this case 60 litres) by 60 (to get the rate per
minute). This gives you a flow rate of 1 litre per minute.
Now run water through the in-line tap where it is to join the hose and adjust
the flow rate until a 1 litre container is filled in 1 minute. The position of the in-line
tap is now set, and can be left connected with the hose. This only needs
to be approximate.
|